Studi Pengaruh Setting Rele Pengaman untuk Meminimalkan Gangguan Sympathetic Trip pada Penyulang Bunisari-Suwung
on
Authors:
I Komang Anom Astana Ady, I Gede Dyana Arjana, Cok Gede Indra Parta
Abstract:
“Sympathetic Trip that happened in the electricity distribution system cause the healthy feeder distrupted because feel a disorder in feeder which affected by a disorder.A residual current that flows as a result of disruption of the one phase to ground on the Bunisari feeder as much as 183,9 A will be perceived by the same phase in the Suwung feeder which has a residual current of 196,9 A, that resulting in the accumulation of capacitive current as much as 380,8 A.The efforts obtained to prevent the Sympathetic trip back with ground fault relay setting as Iset = 25,72 A, tms = 0,11 SI with relay working time for 0,27 seconds and for Suwung feeder is obtained Iset = 24,59 A, tms = 0,115 SI with relay working time for 0,286 seconds.”
Keywords
Keyword Not Available
Downloads:
Download data is not yet available.
References
References Not Available
PDF:
https://jurnal.harianregional.com/jte/full-20384
Published
2016-12-04
How To Cite
ASTANA ADY, I Komang Anom; ARJANA, I Gede Dyana; PARTA, Cok Gede Indra. Studi Pengaruh Setting Rele Pengaman untuk Meminimalkan Gangguan Sympathetic Trip pada Penyulang Bunisari-Suwung.Majalah Ilmiah Teknologi Elektro, [S.l.], v. 15, n. 2, p. 53-58, dec. 2016. ISSN 2503-2372. Available at: https://ojs.unud.ac.id/index.php/jte/article/view/ID20384. Date accessed: 02 Jun. 2025.
Citation Format
ABNT, APA, BibTeX, CBE, EndNote - EndNote format (Macintosh & Windows), MLA, ProCite - RIS format (Macintosh & Windows), RefWorks, Reference Manager - RIS format (Windows only), Turabian
Issue
Vol 15 No 2 (2016): (July - December) Majalah Ilmiah Teknologi Elektro
Section
Articles
Copyright
This work is licensed under a Creative Commons Attribution 4.0 International License
Discussion and feedback