Analisis Pemasangan Filter Pasif untuk Menanggulangi Distorsi Harmonisa Terhadap Beban Non Linier di PT.Wisesa Group
on
88
Teknologi Elektro, Vol. 16, No. 02, Mei - Agustus 2017
Analisis Pemasangan Filter Pasif untuk Menanggulangi Distorsi Harmonisa Terhadap Beban non Linier di PT.Wisesa Group
I Wayan Wahyu Adi Merta1, I Gusti Ngurah Janardana2, I Wayan Arta Wijaya3
Abstract— PT.Wisesa Group is located at No. 199 Jalan Hayam Wuruk Denpasar, PT.Wisesa Group possessed two buildings and one warehouse building where terpasan power of 197 KVA. Almost all electrical equipment is currently based micro-electronics. Equipment of this type is a type of non-linear load. Installation of a passive filter which aims to reduce harmonics that exceeds the standard IEEE 519-1992. In this study conducted a simulation using passive filter type c using software etap, The type of non-linear load, calculate the active power (P) and calculate the load current (IL), simulation of the system before and after the use of passive filters. The analysis showed a passive filter installation cause voltage and current THD content complies with the standards specified IEEE 5191992 is ≤ 5%. Power harmonic distortion at each SDP decreased. C-type passive filter placement is best to lower THD and power distortion, namely the SDP 5 because it can reduce current THD of the total of 31.32% to 3.48%.
Intisari— PT.Wisesa Group terletak di jalan Hayam Wuruk No 199 Denpasar, PT.Wisesa Group mempunya 2 gedung dan 1 bangunan gudang dimana daya yang terpasan sebesar 197 KVA. Hampir semua peralatan listrik yang ada saat ini berbasiskan mikro elektronik. Peralatan jenis ini merupakan jenis beban non linier yang dapat menghasilkan harmonisa tinggi dan dapat mengganggu sistem kelistrikan. Pemasangan filter pasif yang bertujuan untuk meredam harmonisa yang melebihi standar IEEE 519-1992. Dalam penelitian ini dilakukan simulasi penggunaan filter pasif type c menggunakan sofware etap, jenis beban non linear, perhitungan daya aktif (P) dan arus beban (IL), simulasi pada sistem sebelum dan sesudah penggunaan filter pasif. Hasil analisis menunjukkan pemasangan filter pasif menyebabkan kandungan THD arus dan tegangan telah sesuai dengan standar IEEE 519-1992 yang ditentukan yaitu ≤ 5%. Daya distorsi harmonisa pada setiap SDP mengalami penurunan. Penempatan filter pasif type c yang terbaik untuk menurunkan THD dan distorsi daya yaitu pada SDP 5 karena dapat menurunkan THD arus terbesar yaitu 31,32 % menjadi 3,48 %.
Kata kunci— Harmonisa, Distorsi Harmonisa, Beban Non Linier, Filter Pasif Type C
Peningkatan pengoprasian beban-beban non linier signifikan dengan timbulnya distorsi pada sistem daya. Pada sistem tiga phasa elemen elemen non linier akan menimbulkan harmonisa pada rangkaian dan mengakibatkan beban menjadi tak seimbang yang di sebabkan oleh perbedaan nilai phasa R,S,T[1]. Peralatan elektronik yang digunakan untuk menunjang fasilitas seperti AC (Air Conditioner), TV, lampu daylight PLC, alat-alat music, pralatan medis dan lain sebagainya yang dikategorikan sebagai beban nonlinier. Hasil pengukuran THDI didapatkan sebesar 26,8 % yang berarti melebihi nilai standar IEEE 519-1992 yang telah ditentukan yaitu sebesar ≤ 15,0%. Pengukuran THDV sebesar 2,3 %, dimana kondisi tersebut masih memenuhi standar maksimum THDV sebesar ≤ 15%, menurut IEEE Standard 519-1992, untuk mengetahui standar batas maksimum THDi pada utility, maka harus diketahui terlebih dahulu rasio hubung singkat (SCratio). Filter harmonisa merupakan suatu teknologi elektronika daya untuk menghasilkan komponen arus spesifik yang bertujuan untuk meredam arus harmonisa yang dihasilkan oleh beban non linier. Jenis filter yang digunakan dalam penelitian ini merupakan filter pasif type c, dimana filter pasif type c tidak ada rugi-rugi daya fundamental, di reting VAR dan juga tepat untuk memfilter harmonisa rendah maupun tinggi[1], [2].
-
II. HARMONISA
Berdasarkan Standart IEC (International Electrotechnical Commission) 1000.4-11, harmonisa bisa digolongkan kedalam distorsi bentuk-bentuk gelombang[3], karena adanya perubahan bentuk gelombang dari gelombang dasarnya. Harmonisa adalah tegangan dan arus sinusoidal yang mempunyai kelipatan frekuensi sistem tenaga listrik sebagaimana yang dirancang untuk beroperasi di frekuensi 50 Hz atau 60 Hz. Ada empat sebab dasar yang menyebabkan terjadinya harmonisa, yaitu[4]:
-
1. Sumber arus dan tegangan non sinusoidal dan elemen-elemen rangkaian (resistor, induktor, dan kapasitor) adalah linier (independent),
-
2. Sumber arus dan tegangan sinusoidal, sedangkan elemen-elemen rangkaian mengandung elemen nonlinier,
-
3. Sumber arus dan tegangan non sinusoidal, sedangkan elemen-elemen rangkaian non-linier,
-
4. Sumber arus dan tegangan yang berupa sumber DC, sedangkan rangkaiannya mengandung elemen yang berubah secara periodik.
Ada dua criteria harmonisa yaitu distorsi harmonisa arus (THDI) dan harmonisa tegangan (THDV).Harmonisa juga
memiliki batasan yang akan ditentukan dengan perbandingan arus hubung singkat pada PCC (Point of Common Coupling), dan IL dapat disebut arus beban fundamental. Batas harmonisa tegangan sendiri ditentukan dari besarnya tegangan sistem yang terpasang.Standar harmonisa yang diizinkan untuk arus dan tegangan berdasarkan IEEE 519-1992 sesuai dengan Tabel I dan Tabel II[4],[6].
Menurut IEEE Standard 519-1992, untuk mengetahui standar batas maksimum THDI pada utility, maka harus diketahui terlebih dahulu rasio hubung singkat (short-circuit ratio) agar dapat menghitung batas maksimum THDI.
TABEL I
STANDAR HARMONISA UNTUK ARUS DAN TEGANGAN BERDASARKAN IEEE 519-1992 [4]
Maximum Harmonik current Distortion In%IL | ||||||
Individual harmonic Order (Odd Harmonics) | ||||||
ISC / IL |
<11 |
11=<h<17 |
17=<h<23 |
23=<h<35 |
35=<h |
THD% |
<20 |
4 |
2 |
1.5 |
0.6 |
0.3 |
5 |
2050 |
7 |
3.5 |
2.5 |
1 |
0.5 |
8 |
50 100 |
10 |
4.5 |
4 |
1.5 |
0.7 |
12 |
1001000 |
12 |
5.5 |
5 |
2 |
1 |
15 |
>1000 |
15 |
7 |
6 |
2.5 |
1.4 |
20 |
SCratio akan dapat dicari dengan rumus berikut :
SCratio = T^ (1)
‘L
Isc (Arus hubung singkat)akan dapat dicari dengan rumus berikut :
Is C =
kVA ×100
√3 × kV × Z (%)
(2)
IL (Arus beban maksimum)akan dapat dicari dengan rumus berikut :
Il= ™ (3)
-
L PF.√3.KV
Keterangan:
ISC : adalah Arus hubung singkat maksimum pada PCC.
-
IL :adalah Arus beban maksimum.
kW :adalahTotal daya aktif[4],[7].
TABEL II
DISTORTION LIMITS VOLTAGE [1]
Voltage at PCC |
Individual Voltage Distortion (%) |
Total Harmonic Distortion THD (%) |
69 kV |
3,0 |
5,0 |
69 kV – 161 kV |
1,5 |
2,5 |
161 kV |
1,0 |
1,5 |
-
A. BebanNon-linier
Harmonisa akan disebabkan dengan adanya arus beban
non-linier yang impedansinya tidak konstan dalam setiap periode akan tegangan masukannya dengan arus yang dihasilkan tidak bisa berbanding lurus dengan tegangan yang diperoleh. Sehingga nanti beban-beban non-linier tidak mematuhi dan mengikuti Hukum Ohm yang menetapkan arus berbanding lurus dengan tegangan yang di hasilkan[4]. Gelombang tegangan dan arus dan yang dihasilkan oleh beban non-linier maka tidak sama dan menjadi cacat (distorsi) sesuai dengan Gambar 1.
Gambar 1. Arus gelombang dan beban non-linier [5]
-
B. Pemanfaatan Filter Harmonisa
Filter harmonisa biasanya dipasang pada transformator distribusi atau panel kontrol utama. Dengan penambahan filter harmonisa pada suatu sistem tenaga listrik yang mengandung suber-sumber harmonisa, maka penyebaran arus harmonisa ke seluruh jaringan dapat di tekan sekecil mungkin. Secara umum filter harmonisa ada 3 tipe, yaitu filter aktif, filter pasif dan filter hybrid[5].
-
C. Filter Harmonisa Pasif
Filter pasif terdiri dari induktor, kapasitor, resistor (R,L,C) dan unsur-unsur tahanan untuk meredam marmonisa.Type C filter tepat untuk digunakan karena tidak ada rugi-rugi daya fundamental, derating VAR dan juga tepat untuk memfilter pada harmonisa yang tinggi. Type C filter mempunyai dua kapasitor dengan sebuah kapasitor dihubung secara seri dengan resistor dan induktor seperti Gambar 2[5].
I Wayan Wahyu Adi Merta: Analisis Pemasangan Filter Pasif…
p-ISSN:1693 – 2951; e-ISSN: 2503-2372
a 772503 237030l
Gambar 2. Rangkaian Type-C Filter
-
III. METODELOGI PENELITIAN
Penelitian dilakukan di PT. Wisesa Group. Alur analisis langkah penelitian sesuai dengan Gambar 3.
Gambar 3. Langkah penelitian
Tahapan dari Gambar 3 proses analisis pemasangan filter pasif untuk menanggulangi distorsi harmonisa terhadap beban non linier dapat dijelaskan sebagai berikut :
-
1. Pengumpulan Data sistem kelistrikan single line diagram di PT.Wisesa Group.
-
2. Pengumpulan data jumlah beban nonlinear yang terdapat pada setiap gedung dan data hasil pengukuran THD arus dan THD tegangan pada setiap panel.
-
3. Menghitung total kapasitas daya aktif (watt) beban non liniear pada tiap-tiap panel untuk mengetahui standar batas THD (SCratio).
-
4. Menghitung arus hubung singkat (Isc).
-
5. Analisis THD arus dan THD tegangan dengan melakukan simulasi menggunakan software ETAP.
-
6. Membuat model simulasi menggunakan software ETAP.
-
7. Analisis pemasangan filter pasif untuk meredam distorsi dengan mengunakan software ETAP.
-
8. Analisis hasil simulasi berdasarkan IEEE standard 5191992.
-
IV. HASIL DAN PEMBAHASAN
-
A. Sistem Kelistrikan
Sistem kelistrikan di PT.Wisesa Group sesuai dengan gambar single line dibawah.
Gambar 4. Single Line PT.Wisesa Group
Sistem distribusi primer di Gedung PT.Wisesa Group terbagi menjadi satu buah MDP (Main Distribution Panel), pada MDP terdapat tujuh buah SDP (Sub Distribution Panel). Pada sistem distribusi di Gedung PT.Wisesa Group terdapat satu buah transformator tenaga yang menyuplai beban-beban menuju MDP. Dari suplai PLN dengan kapasitas 197 KVA dan Genset dengan kapasitas 200 KVA yang kemudian di distribusikan ke MDP. Dari MDP, daya listrik kemudian disalurkan ke SDP yang selanjutnya disalurkan ke beban atau pemakai.
-
B. Pengelompokan Data Beban Non Linier pada Setiap Gedung
Beban-beban non linier yang terdapat di tiap ruang dikelompokkan terlebih dahulu berdasarkan ruang di setiap gedung. Dari data-data pembebanan listrik pada setiap ruang di Gedung PT.Wisesa Group, diketahui bahwa terdapat 1 buah MDP yang menyuplai daya listrik ke SDP 1, SDP 2, SDP 3, SDP 4, SDP 5, SDP 6, SDP 7.
-
C. Data Hasil Pengukuran THD tegangan dan THD arus
Di bawah dapat dilihat bahwa hampir semua SDP, THDi
Hasil pengukuran tidak sesuai dengan standar yang diperboleh yaitu 15 % seperti pada tabel III di bawah. Sedangkan THDv masih memenuhi standard yaitu di bawah 5%.
TABEL III
HASIL PENGUKURAN THDI DAN THDV DI PT.WISESA GROUP
Tem pat |
Phasa |
Pengukuran THDI (%) di PT.Wisesa Group |
IEEE Standar 519 – 1992 THDI (%) |
KET |
SDP 1 |
R |
10,1 |
5.0 |
Tidak Standar |
S |
9,4 |
5.0 |
Tidak Standar | |
T |
11,5 |
5.0 |
Tidak Standar | |
SDP 2 |
R |
21,4 |
5.0 |
Tidak Standar |
S |
20,9 |
5.0 |
Tidak Standar | |
T |
18,4 |
5.0 |
Tidak Standar | |
SDP 3 |
R |
17,2 |
5.0 |
Tidak Standar |
S |
10,7 |
5.0 |
Tidak Standar | |
T |
14,9 |
5.0 |
Tidak Standar | |
SDP 4 |
R |
16,5 |
5.0 |
Tidak Standar |
S |
14,9 |
5.0 |
Tidak Standar | |
T |
16,6 |
5.0 |
Tidak Standar | |
SDP 5 |
R |
26,8 |
5.0 |
Tidak Standar |
S |
28,3 |
5.0 |
Tidak Standar | |
T |
25,5 |
5.0 |
Tidak Standar | |
SDP 6 |
R |
22,3 |
5.0 |
Tidak Standar |
S |
29,9 |
5.0 |
Tidak Standar | |
T |
27,1 |
5.0 |
Tidak Standar | |
SDP 7 |
R |
11,4 |
5.0 |
Tidak Standar |
S |
14,8 |
5.0 |
Tidak Standar | |
T |
12,4 |
5.0 |
Tidak Standar |
-
D. Menghitung total daya aktif, daya semu dan beban non linier pada tiap-tiap SDP
Daya aktif yang terpasang pada SDP 1 dimana phasa R: 7985 watt, S: 7523 watt, dan T: 7745 watt. Dari hasil pengukuran yang dilakukan pada tiap panel, dengan mengunakan alat ukur didapatkan besar faktor daya pada sistem kelistrikan di Gedung PT.Wisesa Group yaitu 0,85.
Daya Semu (VA) = DayaAfWatt)
= 7.985 = 9.394 VA
0,85
Daya Aktif (W)
Arus beban nonlinier (INL) =
Vi - v - + (V) ∙ pf sistem ( ) p diketahui pf = 0,85
7.985 = 24,64 A
323,5
Kemudian dengan menggunakan metode yang sama akan diperoleh nilai daya semu dan arus beban-beban non linear pada tiap-tiap SDP lainnya dapat di lihat di tabel IV di bawah .
TABEL IV
DAYA AKTIF, DAYA SEMU DAN BEBAN NON LINIER PADA TIAP-TIAP SDP
Tempat |
Phasa |
Daya Aktif (P) |
Daya Semu (S) |
Arus Beban Non Linier (INL) |
Watt |
VA |
Ampere | ||
SDP 1 |
R |
7.985 |
9.394 |
24,64 |
S |
7.523 |
8.850 |
23,25 | |
T |
7.745 |
9.111 |
23,94 | |
SDP 2 |
R |
10.133 |
11.921 |
31,32 |
S |
9.899 |
11,645 |
30,59 | |
T |
10.412 |
12.249 |
32,18 | |
SDP 3 |
R |
4.442 |
5.225 |
13,73 |
S |
3.779 |
4.445 |
11,68 | |
T |
3.887 |
4.572 |
12,01 | |
SDP 4 |
R |
8.441 |
9.930 |
26.09 |
S |
9.213 |
10.838 |
28,47 | |
T |
8.141 |
9.577 |
25.16 | |
SDP 5 |
R |
9.342 |
10.990 |
28.87 |
S |
10.112 |
11.896 |
31,25 | |
T |
9.326 |
10.971 |
28,82 | |
SDP 6 |
R |
6.667 |
7.843 |
20.60 |
S |
6.768 |
7.962 |
20,92 | |
T |
6.845 |
8.052 |
21,17 | |
SDP 7 |
R |
2.322 |
2.731 |
7.17 |
S |
2.431 |
2,860 |
8,84 | |
T |
2,112 |
2.490 |
6.52 |
-
E. Simulasi Analisis THDI dan THDV
Berikut merupakan hasil running simulasi THDI dan THDV pada sistem jaringan PT.Wisesa group menggunakan simulasi software etap.
-
1. Analisis THDI di PT.Wisesa Group
Hasil perhitungan mengenai short-circuit ratio di PT.Wisesa Group maka sesuai dengan IEEE standar 519-1992. Di tabel V di bawah ini hasil running simulasi kandungan THDI pada masing-masing SDP di PT.Wisesa Group.
TABEL V
PERBANDINGAN THDIHASIL RUNNING MENGGUNAKAN SIMULASI DENGAN STANDAR YANG DI TETAPKAN IEEE 519-1992
Tempat |
Hasil running THDI(%) PT.Wisesa Group |
IEEE Standar 519 – 1992 THDImax (%) |
KET |
Gedung I | |||
SDP 1 |
8,98 |
5.0 |
Tidak Standar |
SDP 2 |
8,98 |
5.0 |
Tidak Standar |
SDP 3 |
8,97 |
5.0 |
Tidak Standar |
SDP 4 |
8,97 |
5.0 |
Tidak Standar |
Gedung II | |||
SDP 5 |
34,80 |
5.0 |
Tidak Standar |
SDP 6 |
25,67 |
5.0 |
Tidak Standar |
Gudang | |||
SDP 7 |
12,04 |
5.0 |
Tidak Standar |
I Wayan Wahyu Adi Merta: Analisis Pemasangan Filter Pasif…
p-ISSN:1693 – 2951; e-ISSN: 2503-2372
Tabel V di atas terlihat nilai THDI pada SDP 1 dengan nilai 8,98 %, dan SDP 2 dengan nilai 8,98 %,SDP 3 dengan nilai 8,97 %, SDP 4 dengan nilai 8,97 %,dan nilai persentase THDI terbesar terdapat di SDP 5 sebesar 34,80 %,SDP 6 sebesar 25,67%, SDP 7 sebesar 12,04 %. Masalah ini dikarenakan beban-beban non linier yang terpasang pada SDP 5, dan beban-beban setiap phasa di SDP 5 yang tidak berimbang.
-
2. Analisis THDV di PT.Wisesa Group
Batas maksimum THDV di PT.Wisesa Group menurutt IEEEstandar 519-1992 adalah 5,0 % karena tegangan dibawah 69 KV
Hasil Simulasi mengeluarkan nilai SDP 1 dengan nilai 2,46 %,SDP 2 dengan nilai 2,46 %,SDP 3 dengan nilai 2,46 %, SDP 4 dengan nilai 2,46% dan SDP 5 dengan Nilai 2,46 %,SDP 6 dengan nilai 2,46 %,SDP 7 dengan nilai 2,46 % Berikut ini merupakanhasil running simulasi THDV sesuai dengan tabel VI di bawah.
TABLE VI
PERBANDINGAN THDVDENGAN HASIL RUNNING MENGUNAKAN SIMULASI DENGAN STANDART IEEE 519-1992
Tempat |
Hasil running THDV(%) PT.Wisesa Group |
IEEE Standar 519 – 1992 THDVmax (%) |
KET |
Gedung I | |||
SDP 1 |
2,46 |
5.0 |
Memenuhi Standar |
SDP 2 |
2,46 |
5.0 |
Memenuhi Standar |
SDP 3 |
2,46 |
5.0 |
Memenuhi Standar |
SDP 4 |
2,46 |
5.0 |
Memenuhi Standar |
Gedung II | |||
SDP 5 |
2,46 |
5.0 |
Memenuhi Standar |
SDP 6 |
2,46 |
5.0 |
Memenuhi Standar |
Gudang | |||
SDP 7 |
2,46 |
5.0 |
Memenuhi Standar |
-
3. Running Spectrum Harmonik
Di bawah ini hasil running Spektrum harmonisa dan bentuk gelombang dari semulasi, THDv dan THDi, seperti gambar 5 dan gambar 6 dibawah ini:
Gambar 5. Spektrum harmonic
Gambar 6. Bentuk gelombang
Gambar 5 dan gambar 6 menunjukkan saat jaringan distorsi terdapat beban non linier dan bentuk gelombang sinusoidal mengalami cacat gelombang atau terdistorsi. Spektrum harmonic dan gelombang di simulasikan di SDP yang terdapat kandungan harmonisa tinggi yaitu di SDP 5.
-
F. Analisis THDI pada Setiap SDP dengan Menggunakan Filter Pasif
Untuk meredam distosri harmonisa dalam sistem tenaga, maka perlu mengunakan filter harmonisa yaitu filter pasif. Filter pasif terdiri dari induktor, kapasitor, resistor (R,L,C) dan unsur-unsur tahanan untuk meredam marmonisa. Teknik filter pasif yang menggunakan double tuned filter atau Type-C filter yang memiliki impedansi yang rendah untuk arus harmonisa pada frekuensi tertentu atau frekuensi tinggi atau band-pass filters (damped filters) dapat memfilter harmonisa di atas frekuensi tertentu (frequency bandwidth).
1. Analisis Penempatan Filter Pasif Type C
Penempatan filter pasif pada permodelan sintem klistrikan di PT.Wisesa Group yang di simulasikan di SDP 5 terlihat pada gambar 7.
Hasil analisis THDv sebelum penggunaan filter dan setelah penggunaan filter serta perbandingannya dengan Standar IEEE 152-1992 selengkapnya terlihat pada table VIII.
Gambar 7.Hasil Running Penempatan Filter Pasif di SDP 5
TABEL VIII
PERBANDINGAN HASIL RUNNING THDV TANPA FILTER DAN SESUDAH TERPASANG FILTER
Tempat |
Hasil running THDv (%) Tidak Filter |
Hasil running THDv (%) Terpasang Filter |
IEEE Standar 519 – 1992 THDv(%) |
KET |
Gedung I | ||||
SDP 1 |
2,46 |
2,33 |
5.0 |
Standar |
SDP 2 |
2,46 |
2,33 |
5.0 |
Standar |
SDP 3 |
2,46 |
2,33 |
5.0 |
Standar |
SDP 4 |
2,46 |
2,35 |
5.0 |
Standar |
Gedung II | ||||
SDP 5 |
2,46 |
2,56 |
5.0 |
Standar |
SDP 6 |
2,46 |
2,50 |
5.0 |
Standar |
Gudang | ||||
SDP 7 |
2,46 I |
2,46 I |
5.0 I |
Standar |
Dapat dilihat penambahan filter pasif pada SDP 5 dapat meurunkan THDI sebesar 31,32 %, yang sebelum di tanbahkan filter sebesar 34,80 % dan setelah ditambahkan filter menjadi sesuai standar yaitu 3,48 % dimana standar THDI di PT.Wisesa Group sebesar 5,0 %.
-
2. Analisis THDi di PT.Wisesa Group Setelah di Pasang
Filter Pasif
Hasil analisis THDi sebelum dan setelah penggunaan filter pasif type c serta perbandingannya dengan Standar IEEE 1521992 selengkapnya terlihat pada table VII.
TABEL VII
PERBANDINGAN HASIL RUNNING THDI TANPA FILTER DAN SESUDAH TERPASANG FILTER
Tempat |
Hasil running THDI(%) Tanpa Filter |
Hasil running THDI(%) Terpasang Filter |
IEEE Standar 519 – 1992 THDI (%) |
KET |
Gedung I | ||||
SDP 1 |
8,98 |
3,22 |
5.0 |
Standar |
SDP 2 |
8,98 |
3,83 |
5.0 |
Standar |
SDP 3 |
8,97 |
2,41 |
5.0 |
Standar |
SDP 4 |
8,97 |
3,40 |
5.0 |
Standar |
Gedung |
II | |||
SDP 5 |
34,80 |
3,48 |
5.0 |
Standar |
SDP 6 |
25,67 |
3,30 |
5.0 |
Standar |
Gudang | ||||
SDP 7 |
12,04 |
1,59 I |
5.0 I |
Standar |
-
3. Analisis THDv di PT.Wisesa Group Setelah di Pasang Filter Pasif
-
V. KESIMPULAN
Berdasarkan hasil analisis pemasangan filter pasif untuk menanggulangi distorsi harmonisa terhadap beban non linie di PT.Wisesa Group, maka simpulan yang didapatkan adalah sebagai berikut:
-
1. Kandungan THDi di PT.Wisesa Group sebelum menggunakan filter pasif SDP1 sebesar 8,98%, SDP2 sebesar 8,98%, SDP3 sebesar 8,97%, SDP4 sebesar 8,97%, SDP5 sebesar 34,80%, SDP6 25,67%, SDP7 sebesar 12,04% yang berarti tidak sesuai standar IEEE 519-1992 yang telah ditentukan yaitu sebesar ≤ 5%. Untuk nilai THDv di PT.Wisesa Group sebesar 2,46% dimana kondisi tersebut masih memenuhi standar maksimum THDv IEEE 519-1992 sebesar ≤ 5%.
-
2. Kandungan THDi di PT.Wisesa Group setelah pemasangan filter pasif memenuhi Standar IEEE 5191992 yang telah ditentukan yaitu sebesar ≤ 5 %.
-
3. Penempatan filter pasif yang terbaik untuk menanggulangi distorsi pada simulasi terjadi di SDP 5, karena dapat menurunkan THDi terbesar yaitu sebesar 31,32 % menjadi 3,48 %.
REFERENSI
-
[1] IEEE Std 519-1992, pp. 1–112. Apr. 1993 . IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power System.
-
[2] Waking Antonius Ibi, Rinas I Wayan, Suwardana.2013. Simulasi Penentuan Penempatan Filter Aktif Shunt Untuk Mendapatkan Distorsi Daya Yang terkecil di Blue Point Bay Villa & SPA. Jimbaran: Majalah Ilmiah Teknik Elektro Universitas Udayana Vol 12.
-
[3] R. C. Dugan, M. F. McGranaghan, S. Santoso, and H. W. Beaty. 2012. Electrical Power Systems Quality, Third Edition. McGraw Hill Professional,
I Wayan Wahyu Adi Merta: Analisis Pemasangan Filter Pasif…
p-ISSN:1693 – 2951; e-ISSN: 2503-2372
-
[4] Susiono. juni 2006. Penentuan Lokasi Filter Harmonik Optimum Pada Sistem Distribusi Daya listrik. Jimbaran : Majalah Ilmiah Teknik Elektro Universitas Udayana Vol 5.
-
[5] Sunanda Wahri, Yuli Asmi Rahma. Maret 2012. Aplikasi Filter Pasif Sebagai Pereduksi Harmonik Pada Inverter Tiga Fase. Jurnal Ilmiah Foristek Vol 1.
-
[6] Alexander, Suryajaya. 2011. Pengaruh Total Harmonic Distortion (THD) Pada Suatu Sistem. Semarang: Teknik Elektro Jurusan Teknologi Industri Universitas Katolik Soegijapranata.
-
[7] Samman Faizal Arya, Ahmad Rizkiyanti, Mustafa Mutiah. 2015. Perancangan Simulasi dan Analisis Harmonisa rangkian Inverter Satu Fasa. Makasar: Fakultas Teknik, Jurusan Teknik Elektro. Universitas Hasanuddin,
ISSN 1693– 2951
I Wayan Wahyu Adi Merta: Analisis Pemasangan Filter Pasif…
Discussion and feedback