Studi Analisis Pengaruh Harmonisa Terhadap Rugi-Rugi Daya Pada Penyulang Menjangan
on
Teknologi Elektro, Vol. 16, No1, Januari-April 2017
123
Studi Analisis Pengaruh Harmonisa Terhadap Rugi-Rugi Daya Pada Penyulang Menjangan
-
1I D. G. Wisnu Agung Bayuna, 2I W. Sukerayasa, W. G. Ariastina
Abstract— The content of harmonics on the electrical system if it exceeds the allowed limit will cause some problems, one of them is causing losses in power distribution networks. To determine the effect of harmonics on power losses in the feeder Menjangan, research conducted by the method of measuring the harmonics of each distribution substation in Menjangan feeders with the help of the software for the next simulation. From the results of the identification of patterns and spectrum curves wave harmonic content of the transformer feeder Menjangan, identical with the commercial load as the load of household and electrical appliances are generally supplied from single-phase Switch Mode Power Supplies. From the measurement of harmonics, the highest content contained in distribution substation at the base are GR088 and GR079. The result of the calculation of the difference between the power loss in the condition without the content of harmonics and power loss in situations where the content of harmonics is 1.7991 kW.
Intisari—Kandungan harmonisa pada sistem kelistrikan jika melebihi batas yang diizinkan akan menyebabkan beberapa masalah, salah satunya menimbulkan rugi-rugi jaringan distribusi tenaga listrik. Untuk mengetahui pengaruh harmonisa terhadap rugi-rugi daya di Penyulang Menjangan, dilakukan penelitian dengan metode pengukuran harmonisa pada masing-masing gardu distribusi di Penyulang Menjangan dengan bantuan perangkat lunak untuk selanjutnya dilakukan simulasi. Dari hasil identifikasi pola kurva gelombang dan spectrum kandungan harmonisa pada transformator di Penyulang Menjangan, identik dengan beban komersial seperti beban rumah tangga serta peralatan elektronik yang umumnya disuplai dari single-phase Switch Mode Power Supplies. Dari hasil pengukuran harmonisa, kandungan tertinggi terdapat pada gardu distribusi di bagian pangkal yaitu GR088 dan GR079. Hasil perhitungan selisih antara rugi-rugi daya pada kondisi tanpa kandungan harmonisa dan rugi-rugi daya pada kondisi dengan kandungan hamonisa adalah 1,7991 kW.
Kata Kunci— Kondisi tanpa Harmonisa, Kondisi dengan Harmonisa, Rugi Daya, Penyulang Menjangan.
I. PENDAHULUAN
Penyaluran daya listrik di kawasan Gilimanuk dan sebagian Singaraja disupply oleh Penyulang Menjangan yang bersumber dari Trafo-2 10 MVA Gardu Induk
Gilimanuk. Penyulang ini berbentuk konfigurasi jaringan distribusi 20 kV tipe Radial dengan 69 buah Transformator distribusi.Pada saat ini kondisi Penyulang Menjangan memiliki drop tegangan rata-rata yang cukup tinggi yaitu sebesar 10,22% [1]. Pengukuran awal di tiga gardu pada Penyulang Menjangan menunjukkan bahwa harmonisa arus untuk gardu pangkal (GR 088) = 22,2% [1], gardu tengah (GR 058) = 5% [1], dan gardu ujung (GR 016) = 9,7% [1]. Dari hasil pengukuran awal di tiga gardu tersebut diperoleh hasil harmonisa yang cukup tinggi sebesar 22,2% yang letaknya pada gardu pangkal (GR 088) [1].
Pada penelitian sebelumnya oleh [2] telah mengulas tentang pengaruh distorsi harmonisa pada beban terhadap rugi-rugi transformator yang juga berdampak terhadap unjuk kerja transformator. Penelitian tersebut menganalisis harmonisa dan rugi-rugi daya transformator pada sistem tegangan tinggi 150/20 kV dari berbagai lokasi di gardu induk PT. PLN (Persero) Region Jakarta dan Banten.
Berdasarkan pemaparan permasalahan tersebut, maka dalam penelitian ini menganalisis mengenai pengaruh harmonisa terhadap rugi-rugi daya di sisi tegangan menengah yaitu Penyulang Menjangan. Dengan menggunakan bantuan perangkat lunak untuk simulasi harmonic analysis, selanjutnya hasil analisis yang didapat akan dilakukan perhitungan rugi-rugi daya. Dengan demikian dapat diketahui perbandingan rugi – rugi daya pada saluran saat kondisi tanpa kandungan harmonisa dan saat kondisi dengan kandungan harmonisa pada Penyulang Menjangan.
-
II. Harmonisa PADA SISTEM TENAGA LISTRIK
Harmonik mengacu pada [3], didefenisikan sebagai tegangan ataupun arus sinusoidal yang mempunyai kelipatan frekuensi sistem pasokan tenaga listriknya sebagaimana yang dirancang untuk dioperasikan (50 Hz ataupun 60 Hz). Kemudian menurut [4], mendefenisikan harmonik sebagai tegangan ataupun arus sinusoida yang mempunyai kelipatan bulat dari frekuensi dimana sistem tenaga listrik pasokannya dirancang untuk dioperasikan (atau disebut juga dengan terminology : frekuensi fundamental).
Cacat gelombang yang disebabkan oleh interaksi antara bentuk gelombang sinusoidal sistem dengan komponen gelombang lain dikenal dengan harmonisa. THD didefinisikan sebagai persentase total komponen harmonisa terhadap komponen fundamentalnya. [5]
Harmonisa disebabkan oleh adanya beban nonlinear yang digunakan dalam sistem tenaga listrik. Peralatan seperti converter, penyearah, adjustable speed drive untuk mengendalikan motor-motor industri, thyristor controlled reactor, serta berbagai peralatan yang didasarkan pada proses pensaklaran dapat menimbulkan terjadinya harmonisa. Sedangkan untuk beban, yang dapat menimbulkan harmonisa
antara lain electric arc furnace, induction furnace, serta mesin las, dimana beban tersebut berubah-ubah dari waktu ke waktu dengan cepat secara nonlinier. [6]
-
A. Sumber Harmonisa
Sumber-sumber harmonisa dibagi berdasarkan sumber harmonik dari beban komersial dan sumber harmonik dari beban industri sebagai berikut [7] :
-
• Sumber harmonik dari beban komersial dan fasilitas komersial seperti beban rumah tangga, kantor yang kompleks, pusat perbelanjaan, rumah sakit, dan akses data intern didominasi oleh lampu flourecent dengan ballast elektronik, Pengatur kecepatan (adjustable-speed driver) digunakan pada pemanasan (heating), Ventilasi (Ventilation), dan pendingin ruangan (AC), dan peralatan elektronik sensitive lainnya pada umumnya disuplai dari single-phase switchmode power supplies (SMPS).
Gambar 1: Gelombang Arus dan Spektrum Harmonik pada SMPS
-
• Sumber harmonisa dari kelompok beban industri ini merupakan sumber harmonisa yang sangat penting, karena beban industri pada umunnya menghasilkan harmonisa yang cukup besar dibandingkan dengan beban komersial. Industri sering memanfaatkan fasilitas kapasitor bank untuk memperbaiki faktor daya untuk menghindari biaya penalti. Aplikasi kapasitor untuk perbaikan faktor daya memperbesar harmonik arus dari beban nonlinier, sehingga menimbulkan resonansi.
Gambar 2:Gelombang Arus dan Spectrum Harmonik pada konveterter 3 phasa PWM-type ASD
-
B. Pengaruh Harmonik pada Komponen Sistem Distribusi
Frekuensi harmonik yang lebih tinggi dari frekuensi kerjanya akan mengakibatkan penurunan efisiensi atau terjadi kerugian daya. Secara khusus, efek atau dampak jangka panjang yang ditimbulkan oleh harmonik pada sistem tenaga listrik sebagai berikut [6] :
-
• Pemanasan kapasitor
-
• Tegangan non-sinusoidal yang diterapkan pada mesin listrik dapat meningkatkan rugi inti dan rugi belitan, serta pemanasan lebih.
-
• Frekuensi harmonik yang lebih tinggi dari frekuensi kerjanya akan mengakibatkan penurunan efisiensi dan pada akhirnya mengakibatkan kerugian daya pada transformator.
-
• Pemanasan pada kabel dan peralatan lainnya, rugi-rugi kabel yang dilewati oleh arus harmonik akan semakin besar.
-
C. Rugi-Rugi pada Penghantar
Rugi-rugi yang terjadi pada penghantar bergantung terhadap besar arus yang mengalir padanya dan besar tahanan yang dimiliki penghantar tersebut. Dengan mengalirnya arus harmonisa (Irms) pada penghantar, maka akan menyebabkan terjadinya penambahan panas sehingga terjadi peningkatan rugi-rugi I2R pada penghantar tersebut. Dengan demikian besarnya rugi-rugi penghantar (PLoss) akibat terdapatnya komponen harmonisa di dalam arus beban dapat dihitung [8] :
Si
‰ss = V ⅛ R n
Π = L [8] (1)
dengan:
PLoss = rugi-rugi penghantar (watt)
In = arus komponen harmonisa (ampere)
Rn = tahanan untuk frekuensi harmonik (ohm)
-
D. Rugi-Rugi pada Transformator
Rugi-rugi transformator dikelompokkan menjadi rugi tanpa beban dan rugi berbeban (load losses). Rugi-rugi transformator keseluruhan sebagai berikut [2] :
PTL = PNL + PLL [2] (2)
dengan:
PTL = rugi total transformator
PNL = rugi tanpa beban
PLL = rugi berbeban
-
1) Rugi Transformator Tanpa Beban : Susut trafo tanpa beban (beban nol) terdiri dari susut eddycurrent (PEC) dan susut hysterisis. Susut eddy current adalah besaran dari eddy current yang dihasilkan oleh tegangan induksi pada laminasi sebagai respon terhadap alternating flux yang merupakan proporsional dari kuadrat ketebalan laminasi, kuadrat dari frekuensi dan kuadrat dari nilai efektif (rms) kerapatan flux. Menurut [9], susut tanpa beban tidak berpengaruh terhadap arus harmonisa.
-
2) Rugi Transformator Berbeban : Perhitungan yang digunankan untuk rugi-rugi transformator pada ratingnya dalam per-unit (pu). [2]
PLL-R (pu) = 1 + PEC-R (pu) + POSL-R (pu) [2] (3)
dengan:
PLL-R = rugi berbeban pada rating transformator.
PEC-R = rugi arus eddy pada belitan pada rating trafo
POSL-R = rugi sasar lain pada rating transformator
Untuk menghitung kemampuan transformator menggunakan data desain, mengacu kepada [10] dan [11], maka rugi transformator karena mengalirnya arus beban melalui belitan transformator.
Rugi Ohmik (I2R), akibat arus beban mengalir pada konduktor atau belitan dan ini disebut “Rugi dc”.
PI2R-R = K . [(I1-R)2.R1] + [(I2-R)2.R2] watt [10] (4)
dengan:
PI2R-R = rugi Ohmik pada rating transformator.
K = 1.5 untuk transformator tiga phasa.
I1-R = rating arus pada sisi tegangan tinggi primer.
I2-R = rating arus pada sisi tegangan rendah sekunder.
R1 = nilai resistansi (3 phasa) pada sisi tegangan tinggi.
R2 = nilai resistansi (3 phasa) pada sisi tegangan rendah.
Rugi Sasar/Stray Losses (PTSL-R) merupakan rugi-rugi transformator berbeban (PLL-R) dikurangi Rugi Ohmik atau Rugi dc (PI2R-R).
PTSL-R = PLL-R – {K . [(I1-R)2.R1] + [(I2-R)2.R2]} watt [11] (5)
dengan :
K = 1.5 untuk transformator tiga phasa
PTSL-R = rugi sasar total sesuai rating
PLL-R = rugi berbeban sesuai rating
R1 = nilai resistansi (3phasa pada sisi tegangan tinggi
R2 = nilai resistansi (3phasa) pada sisi tegangan rendah
I1-R = rating arus pada sisi tegangan tinggi primer
I2-R = rating arus pada sisi tegangan rendah sekunder
Asusmsi yang digunakan mengacu pada [12] untuk type transformator dengan pendingin minyak, untuk mendapatkan rugi arus eddy (PEC-R).
PEC-R = PTSL-R x 0.33 watt [12] (6)
Rugi sasar lain (POSL) pada inti dan metal serta dinding transformator akibat terpotongnya fluks sasar.
POSL-R = PTSL-R – PEC-R watt [12] (7)
dengan :
POSL-R = rugi sasar lain sesuai ratingnya
PTSL-R = rugi sasar total sesuai ratingnya
PEC-R = rugi arus eddy sesuai ratingnya
Faktor harmonisa arus eddy belitan didapatkan dengan:

[2]
(8)
dengan :
FHL = faktor harmonisa untuk rugi arus eddy belitan.
n = harmonisa orde ke-n
In = arus dengan komponen harmonisa ke-n
I1 = arus beban fundamental (ampere)
Faktor harmonisa untuk rugi sasar lain diperoleh dengan

[2] (9)
dengan :
FHL-STR = Faktor harmonisa untuk rugi sasar lain.
n = Harmonisa orde ke-n
In = Arus dengan komponen harmonisa ke-n
I1 = Arus beban fundamental (ampere)
Rugi transformator berbeban dengan adanya harmonisa.
PLL (pu) = PI2R-n + [(FHL × PEC) + (FHL-STR × POSL)] [2] (10)
dengan :
PLL =Total Rugi Transformator Berbeban Akibat Harmonisa (watt)
Pi2r-∏ = Rugi dc I2R harmonisa (watt)
FHL = faktor harmonisa untuk rugi arus eddy belitan
PEC = rugi arus eddy belitan pada transformator berbeban (watt)
FHL-STR = faktor susut akibat arus harmonisa pada other stray loss
POSL = rugi sasar lain pada transformator berbeban (watt)
-
III. METODE PENELITIAN
Dalam penelitian ini dilakukan pengukuran kandungan harmonisa pada masing-masing transformator di Penyulang Menjangan. Dari pengukuran kandungan harmonisa tersebut akan didapatkan hasil pengukuran berupa arus, tegangan, cos φ , harmonisa arus (THDi).
Simulasi harmonic analysis menggunakan bantuan perangkat lunak ETAP PowerStation. Selanjutnya hasil dari eksekusi simulasi harmonic analysis tersebut berupa arus fundamental dan arus r.m.s (arus dengan kandungan harmonisa). Arus fundamental digunakan untuk menghitung rugi-rugi daya penghantar pada kondisi tanpa kandungan harmonisa, sedangkan arus r.m.s akan digunakan untuk perhitungan rugi-rugi daya penghantar dalam kondisi dengan kandungan harmonisa. Selanjutnya berdasarkan data hasil pengukuran harmonisa pada transformator, dilakukan perhitungan rugi-rugi daya pada masing-masing transformator dalam kondisi tanpa kandungan harmonisa dan kondisi dengan kandungan harmonisa.
IV.PEMBAHASAN
-
A. Gambaran Umum Penyulang Menjangan
Salah satu wilayah kerja PT. PLN (Persero) Distribusi Bali Area Bali Utara yang memiliki cakupan yang cukup luas dan panjang yakni berada di daerah Gilimanuk menuju Gerokgak-Singaraja. Daerah tersebut merupakan salah satu daerah di wilayah bali utara dengan tingkat pertumbuhan penduduk dan perkembangan industri pariwisata yang semakin meningkat, sehingga kebutuhan akan listrik semakin meningkat.
Kebutuhan listrik untuk daerah Gilimanuk dan Gerokgak-Singaraja tersebut disuplai dari GI Gilimanuk melalui transformator II melalui Penyulang Menjangan dimana dalam keadaan normal Penyulang Menjangan beroperasi secara radial yang terdiri dari 69 transfornator distribusi yang tersebar sepanjang salurannya, serta panjang salurannya mencapai 64,373 km.
-
B. Hasil Pengukuran THD Penyulang Menjangan
Data hasil pengukuran THD yang digunakan dalam penelitian ini adalah Total Harmonic Distortion arus (THDi). Dari data hasil pengukuran THDi dapat diketahui bahwa nilai kandungan harmonisa arus tertinggi yang terukur terdapat

pada Transformator di bagian pangkal Penyulang Menjangan yaitu GR088 dan GR079 yang dapat dilihat pada table I berikut.
TABEL I
DATA HASIL PENGUKURAN THD PENYULANG MENJANGAN
Harmonisa (%) |
Uraian Transformator | |||||
GR088 (100 kVA) |
GR079 (160kVA) | |||||
R |
S |
T |
R |
S |
T | |
THDi |
27,56 |
24,70 |
23,60 |
21,47 |
22,70 |
31,80 |
n=3 |
21,9 |
20,4 |
19,5 |
18,3 |
19,4 |
26,2 |
n=5 |
12,3 |
12,6 |
10,3 |
9,5 |
10,6 |
15,1 |
n=7 |
8,0 |
7,8 |
7,7 |
5,8 |
6,2 |
11,4 |
n=9 |
6,9 |
3,6 |
6,0 |
1,3 |
3,9 |
7,9 |
n=11 |
3,8 |
0,6 |
2,8 |
0,3 |
1,5 |
3,8 |
n=13 |
0,9 |
1,2 |
0,2 |
0,1 |
0,5 |
0,8 |
n=15 |
1 |
0,9 |
1,2 |
0,7 |
0,7 |
0,8 |
n=17 |
0,7 |
0,5 |
0,3 |
0 |
0,3 |
0,3 |
n=19 |
0,3 |
0,6 |
0,8 |
0,3 |
0,4 |
0,9 |
-
C. Analisis Harmonic Load Flow dengan Program ETAP PowerStation
Langkah awal yang dilakukan adalah dengan menggambar secara kesuluruhan diagram segaris Penyulang Menjangan selanjutnya memasukan data – data yang diperlukan yaitu : data beban Jaringan Tegangan Menengah, data hasil pengukuran THDi, data panjang, diameter, impedansi, dan jenis penghantar kemudian dilakukan running harmonic analysis load flow pada ETAP PowerStation yang nantinya menghasilkan nilai arus fundamental dan juga arus r.m.s (Irms) saluran. Data hasil eksekusi program ETAP PowerStation didapatkan saluran MVTIC 1 yang memiliki nilai tertinggi yang dapat dilihat pada table II.
TABEL II
DATA HASIL PROGRAM ETAP HARMONIC ANALYSIS
Uraian Saluran |
Arus Fundamental (Ampere) |
Arus r.m.s (Ampere) | ||||
R |
S |
T |
R |
S |
T | |
MVTIC 1 |
88,86 |
88,86 |
88,86 |
89,39 |
89,39 |
89,39 |
-
D. Perhitungan Rugi-Rugi Penghantar Kondisi Tanpa
Kandungan Harmonisa
Arus fundamental merupakan arus yang mengalir pada penghantar/saluran yang tidak mengandung harmonisa, sehingga arus fundamental yang telah didapatkan dari hasil eksekusi program ETAP Harmonic Analysis akan digunakan dalam menganalisis rugi-rugi penghantar pada kondisi tanpa harmonisa yang mengacu pada (1), dimana In (Arus Harmonisa) diganti dengan menggunakan arus fundamental. Sebagai contoh perhitungan rugi-rugi daya pada penghantar MVTIC 1 sebagai berikut.
Rugi – rugi daya tiga phasa pada saluran MVTIC 1 kondisi tanpa harmonisa :
I (arus fundamental) = 88,86 A.
L (panjang penghantar) = 6784 m = 6,784 km.
= 0,265 Ω/km . 6,784 km
R (Tahanan)
AP
= 1,79776 Ω
1"11 =- 0
= 3 x (Ifundamental) . R
= 3 x (88,86)2 x 1,79776
= 42585,876 Watt
= 42,5859 kW
Rugi-rugi daya saluran line/cable MVTIC 1 sebesar 42,5859 kW. Dengan cara perhitungan yang sama seperti di atas, dapat dianalisis rugi-rugi total saluran pada Penyulang Menjangan kondisi tanpa kandungan harmonisa adalah sebesar 199,6573 kW.
-
E. Perhitungan Rugi-Rugi Transformator Kondisi Tanpa Kandungan Harmonisa
Dalam perhitungan rugi daya kondisi tanpa harmonisa maka yang digunakan hanya harmonisa arus orde pertama saja (fundamental). Sebagai contoh perhitungan rugi-rugi daya pada Trafo GR88 dengan kapasitas trafo adalah 100 kVA sebagai berikut.
Diketahui data Transformator GR088 sesuai rating adalah sebagai berikut :
Rugi tanpa beban (PNL) = 210 Watt
Rugi berbeban (PLL) = 1420 Watt
Resistan sisi primer (R1) = 182 Ω
Arus sisi primer (I1) = 2.89 Amp
Resistan sisi primer (R2) = 0.0027 Ω
Arus sisi primer (I2) = 151.94 Amp
Mengacu pada (5) didapatkan total rugi sasar sesuai rating transformator sebagai berikut :
PTSL-R = PLL-R – {K . [(I1-R)2.R1] + [(I2-R)2.R2]}
= 1420 – {1,5 x [(2,89)2 x 0,182]+[(151.94)2 x 0,0027]}
= 1324,222534 Watt
PEC-R = PTSL-R x 0.33
= 1324,222534 x 0.33
= 436,993436 Watt
POSL-R = PTSL-R – PEC-R
= 1324,222534 - 436,993436
= 887,2291 Watt
PLL-R = PI2R-R + PEC-R + POSL-R
1420 = PI2R-R + 436,993436 + 887,2291
PI2R-R = 95,777 Watt
TABEL III
PERHITUNGAN FAKTOR RUGI HARMONISA TRASFORMATOR GR088 PENYULANG MENJANGAN DALAM (pu) KONDISI TANPA KANDUNGAN HARMONISA
Orde (n) |
(In/I1) |
(In/I1)2 |
(n2) |
(In/I1)2*n2 |
(n0.8) |
(In/I1)2*n0.8 |
1 |
1,000 |
1,000 |
1 |
1,000 |
1,000 |
1,000 |
TOTAL |
1,000 |
1,000 |
1,000 |
Dari table III didapatkan :

1.000/1.000 = 1j000 pu

1.000/1,000 = 1j000 pu
Untuk transformator yang dibahas dalam penelitian ini adalah transformator yang menggunakan minyak, beban transformator GR88 tercatat 36,67 % dari kapasitasnya sehingga formula yang digunakan dalam perhitungan untuk menentukan maksimum arus yang dibebankan pada transformator adalah :
^⅛⅛:) =
0.3667

(0,3667)2x(l,0 00)z = Pll
Pll = 0,134469 (pu)
Rugi – rugi daya tiga phasa pada saluran MVTIC 1 kondisi dengan kandungan harmonisa.
Irms (Arus harmonisa) = 89,39 A.
L (Panjang penghantar) = 6784 m = 6,784 km.
R (Tahanan) = 0,265 Ω/km . 6,784 km = 1,79776 Ω
δp=3xELar")
= 3 x (Irms)2 . R
= 3 x (89,39)2 x 1,79776
= 43095,393 Watt
= 43,0954 kW
Rugi-rugi daya saluran line/cable MVTIC 1 sebesar 43,0954 kW. Dengan cara perhitungan yang sama seperti di atas, dapat dianalisis rugi-rugi total saluran pada Penyulang Menjangan kondisi dengan kandungan harmonisa adalah sebesar 200,7624 kW.
G. Perhitungan Rugi-Rugi Transformator Kondisi Dengan
Kandungan Harmonisa
Perhitungan pengaruh harmonisa mengacu pada standar internasional (IEEE Std C57.110TM-2008). Untuk harmonisa kelipatan 3 seperti 3,6,9,12,15 dan seterusnya tidak dimasukkan dalam perhitungan, karena hanya berpengaruh pada besarnya ukuran luas penampang konduktor pada titik netral. Sebagai contoh perhitungan rugi-rugi daya pada Trafo GR088 dengan kapasitas trafo adalah 100 kVA sebagai berikut.
TABEL IV
HASIL PERHITUNGAN RUGI-RUGI DAYA TRANSFORMATOR GR088 PENYULANG MENJANGAN DALAM KONDISI TANPA KANDUNGAN HARMONISA
Type Rugi-Rgi |
Rugi sesuai Rating (Watt) |
Rugi sesuai Beban Trafo (Watt) |
Faktor Harmonisa (pu) |
Koreksi Rugi-Rugi (Watt) |
Tidak berbeban |
210 |
210 |
210 | |
Rugi Ohmik (I2R) |
95,777 |
12,879 |
12,879 | |
Rugi arus eddy |
436,993436 |
58,762 |
1,000 |
58,762 |
Rugi Sasar Lain |
887,2291 |
119,305 |
1,000 |
119,305 |
Rugi Total |
400,946 |
TABEL V
PERHITUNGAN FAKTOR RUGI HARMONISA TRASFORMATOR GR088 PENYULANG MENJANGAN DALAM (pu) KONDISI DENGAN KANDUNGAN HARMONISA
Orde (n) |
(In/I1 ) |
(In/I1)2 |
(n2) |
(In/I1)2* n2 |
(n0.8) |
(In/I1)2*n0 .8 |
1 |
1,000 |
1,000000 |
1 |
1,000000 |
1,0000 |
1,000000 |
5 |
0,126 |
0,015876 |
25 |
0,396900 |
3,6239 |
0,057533 |
7 |
0,078 |
0,006084 |
49 |
0,298116 |
4,74328 |
0,028858 |
11 |
0,006 |
0,000036 |
121 |
0,004356 |
6,80948 |
0,000245 |
13 |
0,012 |
0,000144 |
169 |
0,024336 |
7,78314 |
0,001121 |
17 |
0,005 |
0,000025 |
289 |
0,007225 |
9,64626 |
0,000241 |
19 |
0,006 |
0,000036 |
361 |
0,012996 |
10,5439 |
0,000380 |
Total |
1,022201 |
1,743929 |
1,088378 |
Berdasarkan hasil perhitungan pada tabel IV diketahui rugi-rugi daya total transformator GR088 Penyulang Menjangan sesuai beban transformator dalam kondisi tanpa harmonisa yaitu sebesar 400,946 Watt. Dengan cara perhitungan yang sama, dapat dianalisis rugi-rugi daya untuk total transformator di Penyulang Menjangan dalam kondisi tanpa harmonisa yaitu sebesar 44708,180 Watt atau sama dengan 44,708 kW.
F. Perhitungan Rugi-Rugi Penghantar Kondisi Dengan
Kandungan Harmonisa
Untuk menghitung rugi-rugi daya saluran dengan kandungan harmonisa yang mengacu pada (5), dimana In yang dipakai adalah arus r.m.s (Irms) hasil eksekusi simulasi program ETAP. Sebagai contoh perhitungan rugi-rugi daya pada penghantar MVTIC 1 sebagai berikut.
Dari table V didapatkan :

1,743929/1,022201 = 1,705053 pa

1,DSS37S∕1,0222 01 = 1..06474 pu
Beban transformator GR88 tercatat 36,67 % dari kapasitasnya sehingga :

0,3667 = 1∕⅛∕√ 1,022201

Pll = 0,137454 (pu)
TABEL VI
HASIL PERHITUNGAN RUGI-RUGI DAYA TRANSFORMATOR GR088 PENYULANG MENJANGAN DALAM KONDISI TANPA KANDUNGAN HARMONISA
Type Rugi-Rgi |
Rugi sesuai Rating (Watt) |
Rugi sesuai Beban Trafo (Watt) |
Faktor Harmonisa (Watt) |
Koreksi Rugi-Rugi (Watt) |
Tidak berbeban |
210 |
210 |
210 | |
Rugi Ohmik (I2R) |
95,777 |
13,165 |
13,165 | |
Rugi arus eddy |
436,993436 |
60,067 |
1,706053 |
102,4768 |
Rugi Sasar Lain |
887,2291 |
121,953 |
1,06474 |
129,849 |
Rugi Total |
455,490 |

Gambar 1: Tampilan kurva gelombang dan spectrum harmonisa pada transformator GR088 Penyulang Menjangan
H. Perbandingan Hasil Perhitungan Rugi-Rugi Daya Total
Total beban sesuai data hasil pengukuran beban transformator Penyulang Menjangan oleh PT. PLN (Persero) Rayon Gilimanuk sebesar 3665,91 kVA dengan cos phi sebesar 0,946 sehingga total beban adalah 3493,608 kW. Besarnya rugi – rugi daya pada jaringan distribusi Penyulang Menjangan jika dinyatakan dalam prosentase adalah sebagai berikut.
Total rum days nd iarirι≡an distribusi
% Ruej days = ——r÷r-√----—r--:—— x 100%
' Total Eabar Ronsuimer Zhstrtbusi
Perbandingan hasil perhitungan rugi – rugi daya di Penyulang Menjangan terlihat pada table VII.
TABEL VII
PERBANDINGAN RUGI – RUGI DAYA DI PENYULANG
MENJANGAN
Nama Penyulang |
Kondisi |
Rugi Saluran (kW) |
Rugi Trafo (kW) |
Rugi Daya Total (kW) |
Rugi Daya Total (%) |
Menjangan |
Tanpa Harmonisa |
199,6573 |
44,708 |
244,3653 |
6,995 |
Menjangan |
Harmonisa |
200,7624 |
45,402 |
246,1644 |
7,046 |
Selisih |
1,7991 |
Gambar 2: Tampilan kurva gelombang dan spectrum harmonisa pada transformator GR088 Penyulang Menjangan
Dari gambar 1 dan 2 terlihat pola kurva gelombang dan spectrum pada GR088 dan GR079 identik dengan sumber harmonik dari Beban Komersial dan Fasilitas komersial seperti beban rumah tangga, kantor yang kompleks, pusat perbelanjaan, rumah sakit, dan akses data intern didominasi oleh lampu flourecent dengan ballast elektronik, Pengatur kecepatan (adjustable-speed driver) digunakan pada pemanasan (heating), Ventilasi (Ventilation), dan pendingin ruangan (AC) dan peralatan elektronik sensitive lainnya pada umumnya disuplai dari single-phase switchmode power supplies. Namun selain dari beban sumber penyebab timbulnya harmonisa, perlu dipertimbangkan juga aspek polusi yang dapat menimbulkan partial discharge pada isolator, sehingga berpengaruh terhadap besarnya harmonisa.
-
IV. KESIMPULAN
Berdasarkan pembahasan yang telah dilakukan terebut, dapat diambil beberapa kesimpulan sebagai berikut :
-
1. Dari hasil pengukuran kandungan harmonisa arus pada Penyulang Menjangan diketahui transformator distribusi pada pangkal penyulang yaitu GR088 dan GR079, memiliki kandungan harmonisa arus yang tertinggi.
-
2. Rugi-rugi daya pada Penyulang Menjangan dipengaruhi oleh kandungan harmonisa arus dengan selisih antara rugi-rugi daya pada kondisi tanpa kandungan harmonisa dan rugi-rugi daya pada kondisi dengan kandungan hamonisa adalah 1,7991 kW. Selisih rugi-rugi daya tersebut disebabkan oleh perbedaan arus fundamental dan arus harmonisa yang mengalir pada jaringan sistem distribusi 20 kV Penyulang Menjangan akibat adanya kandungan harmonisa arus.
-
3. Berdasarkan pola kurva gelombang dan spectrum kandungan harmonisa pada transformator GR088 dan GR079 di Penyulang Menjangan, sumber harmonisa identik dengan pola kurva gelombang dan spectrum yang dihasilkan dari Beban Komersial dan Fasilitas komersial seperti beban rumah tangga serta peralatan elektronik sensitive yang pada umumnya disuplai dari single-phase switchmode power supplies (SMPS).
UCAPAN TERIMAKASIH
Pertama-tama perkenankanlah penulis memanjatkan puji syukur ke hadapan Ida Sang Hyang Widhi Wasa/ Tuhan Yang Maha Esa, karena hanya atas asung wara nugraha-Nya/kurnia-Nya, skripsi ini dapat diselesaikan. Penulis mengucapkan terima kasih yang sebesar-besarnya kepada Dekan Fakultas Teknik Universitas Udayana yang dijabat oleh Bapak Prof. Ir. Ngakan Putu Gede Suardana, MT., Ph.D., atas kesempatan yang diberikan kepada penulis untuk menjadi mahasiswa pada Fakultas Teknik Universitas Udayana. Ucapan terima kasih ini ditujukan kepada Bapak Ir. I Wayan Sukerayasa, MT., pembimbing I dan Bapak Wayan Gede Ariastina, ST., MengSc., Ph.D., Pembimbing II yang dengan penuh perhatian telah memberikan dorongan, semangat, bimbingan, dan saran selama penulis mengikuti program sarjana. Terima kasih sebesar-besarnya pula penulis sampaikan kepada orang tua, adik, pacar, dan teman-teman yang dengan penuh pengorbanan telah memberikan kepada penulis kesempatan untuk lebih berkonsentrasi menyelesaikan tugas akhir ini.
REFERENSI
-
[1] PT. PLN(Persero). “Susut Distribusi Bali tahun 2015”. Bali. 2015
-
[2] Sumaryadi, “Management Asset, Upaya Mempertahankan Unjuk Kerja Transformator Terhadap Pengaruh Harmonisa Pada Sistem Tenaga Listrik”. Bandung : Program Studi Magister Teknologi dan Bisnis Kelistrikan Institut Teknologi Bandung. 2009.
-
[3] International Electrotechnical Commision (IEC) 6100-2-11990, “Electromagnetic Compatibility”, 1990.
-
[4] IEEE 1159-1995 standard", IEEE Recommended Practices for Monitoring Electric Power Quality,”1995.
-
[5] Rinas. I. W. “Penggunaan Metode Urutan (Sequence Method) Pada Analisis Harmonisa Untuk Sistem Kelistrikan Tak-Seimbang”. Staf Pengajar Teknik Elektro Fak. Teknik Universitas Udayana, Jimbaran Bali.2007
-
[6] A.I. Weking , I W. Rinas, A. K. Suwardana, “Simulasi Penentuan Penempatan Filter Aktif Shunt Untuk Mendapatkan Distorsi Daya Yang Terkecil Di Blue Point Bay Villa & Spa”. 2013
-
[7] Dugan, Rizy, “Harmonic Considerations for Electrical Distribution Feeders”, National Technical Information Service, Report No. ORNL/Sub/81-95011/4 (Cooper Power Systems as Bulletin 87011, “Electrical Power System Harmonics, Design Guide”). 2001.
-
[8] Syahwil M, dkk. “Studi Dampak Harmonisa Terhadap Susut Teknis Pada Industri Semen (Kasus Industri Semen Tonasa)”. Makassar : Magister Student of Hasanuddin University. 2010.
-
[9] Arrillaga, J. and Watson, N. R, “Power System Harmonic Analysis. New Zealand”. University of Canterbury. 2000.
-
[10] IEEE Std C57.91-1993, ”Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers and Guide for Short-Circuit Testing”, 1993
-
[11] IEEE Std C57.91-1995,”Loading Guide for Mineral Oil Immersed”, 1995
-
[12] IEEE Std C57.110TM-1998,”Recommended Practice for Establishing Liquid-Filled and Dry-Type Power and Distribution Transformer Capability When Supplying Nonsinusoidal Load Current”, 2008.
{ halaman ini sengaja dikosongkan }
I D. G. Wisnu Agung Bayuna: Studi Analisis Pengaruh Harmonisa p-ISSN:1693 – 2951; e-ISSN: 2503-2372